Oświetlenie ewakuacyjne - przepisy, wymagania, pomiary i schemat, czyli wszystko, co warto wiedzieć

Escape Lighting in Poland: Regulations, Requirements, Measurements and Diagram

Escape lighting is a special type of lighting whose main purpose is to ensure safe and effective evacuation from a building in an emergency. It is a key element of building safety systems. If the normal light source fails, escape lighting must be able to operate independently so that people can leave the building safely. This lighting is usually powered by a battery that is not fed from the main lighting supply. Escape lighting is required in all rooms where people are present, as well as on escape routes. It must be properly designed and installed to make it easier to move around any obstacles and to lead to a safe exit outside the building. What are the key requirements for escape lighting in buildings? What are the rules on measurement and maintenance of escape lighting? 

What is the difference between emergency lighting and escape lighting? 

Emergency lighting, according to the PN-EN 1838 standard, is a lighting installation that includes escape lighting. Emergency lighting should operate when other light points go out as a result of a failure or an interruption to the electricity supply. For this reason, emergency lighting should be powered from a source independent of the general supply. Emergency lighting is divided into: 

  • Escape lighting; 
  • Escape route lighting; 
  • Open area (anti-panic) lighting; 
  • High-risk task area lighting; 
  • Standby lighting. 
Type of emergency lightingStandards / key requirements
Escape lightingPN-EN 50172, PN-EN 60598-2-22, PN-EN 62034; duration: 1 hour
– Escape route lightingMin. 1 lx along the centre line of the escape route; uniformity max/min 40:1; switch-on: 50% of illuminance within 5 s, 100% within 60 s
– Open area (anti-panic) lightingMin. 0.5 lx on the floor of the open area; uniformity max/min 40:1; switch-on: 50% within 5 s, 100% within 60 s
– High-risk task area lightingMin. 10% of normal illuminance (En), not less than 15 lx; uniformity Emax/Emin 10:1; switch-on: 100% within 0.5 s
– Safety signsPN-EN ISO 7010, ISO 3864-1, ISO 3864-4; luminance Lmin 2 cd/m²; uniformity Lmax/Lmin ≤ 10:1; contrast 5:1 < Lc/Lsc < 15:1
Standby lightingE ≥ 100% En (illuminance at least equal to normal lighting)

Types of emergency lighting (according to PN-EN 1838:2013. Lighting applications. Emergency lighting)

Escape lighting, whose general purpose is to ensure safety when leaving a location in the event of a failure of the normal power supply, consists of the following three types of lighting: 

– escape route lighting, whose purpose is to ensure safety while people are leaving the premises by creating visual conditions that allow escape routes to be identified and used, and fire-fighting and safety equipment to be easily located and used, 

– open area lighting (anti-panic lighting), whose purpose is to reduce the likelihood of panic and to enable people heading towards escape routes to move safely, by providing visual conditions that allow them to reach a place from which an escape route can be recognised; as part of this type of lighting, it is recommended that obstacles up to a height of 2 m (measured from the floor) are also illuminated, 

– high-risk task area lighting, whose purpose is to improve the safety of people involved in a potentially dangerous process or situation, and to enable the proper termination of activities in a way that ensures the safety of people in that area. 

Technical parameters that escape lighting must meet: 

According to the PN-EN 1838:2005 standard on the application of emergency lighting, escape lighting must meet the following criteria: 

a) The illuminance E on the centre line of the escape route should be at least 1 lx. 

b) Along the centre line of the escape route, the ratio of Emax. to Emin. should not exceed 40. 

c) At floor level, in the unobstructed area of an active open area, the illuminance E should be at least 0.5 lx. 

d) In the open area, the ratio of Emax. to Emin. should not exceed 40. Note that these requirements must also be met at the end of the specified operating time of the escape lighting. 

e) In a high-risk task area, the illuminance of the escape lighting on the reference plane should not be less than 10% of the maintained basic illuminance required for the given tasks, and must be at least 15 lx. 

f) In a high-risk task area, the uniformity of illuminance, i.e. the ratio of average E to Emax., should be at least 0.1. 

g) To ensure adequate illuminance, escape lighting luminaires should be mounted at least 2 m above the floor. 

  • at every exit door intended for evacuation, 
  • near stairs, so that each step is directly illuminated, 
  • near every change of level, 
  • mandatorily at emergency exits and safety signs, 
  • at every change of direction, 
  • at every intersection of corridors, 
  • outside and near every final exit, 
  • near every first aid point, 
  • near every fire-fighting device and alarm call point. 

Signs at all emergency exits and along escape routes should be illuminated so that they unambiguously indicate the escape route to a place of safety. Note: first aid points, fire-fighting devices and alarm call points should be illuminated so that the illuminance on the floor near them is at least 5 lx (“near” means within 2 m, measured horizontally). 

Principles and functions of an emergency escape lighting system 

Standby lighting is an integral part of the emergency lighting system, enabling normal activities to continue without major changes. 

In the context of an emergency escape lighting system, we can distinguish four types of emergency situation that may occur in a building: 

  • when the primary power supply is available and there is no smoke, the system does not need to be active, 
  • when the primary power supply is lost but there is no smoke, the system must be active, 
  • when the primary power supply is available but there is smoke, the system must be active, 
  • when the primary power supply is lost and there is smoke, the system must be active. 

The main purpose of emergency escape lighting is to provide immediate, automatic and sufficiently long-lasting illumination of a specified area when the power supply to the normal lighting fails. The emergency escape lighting system should perform the following tasks: 

  • illuminate signs indicating the escape route, 
  • provide adequate illuminance on escape routes to allow safe movement to a place of safety, 
  • make it easy to locate and use fire alarm points and fire-fighting equipment placed along escape routes, 
  • enable safety-related actions to be carried out. 

Legal provisions on escape lighting 

Presented below are the various legal acts that define precisely how escape and emergency lighting systems should be designed, installed and monitored:  

1) Act of 24 August 1991 on fire protection. 

2) Regulation of the Minister of the Interior and Administration of 20 June 2007 on the list of products used to ensure public safety or to protect health, life and property, and on the rules for issuing approvals for the use of such products 

3) Regulation of the Minister of Infrastructure of 12 March 2009 amending the regulation on the technical conditions that buildings and their location should meet 

4) Regulation of the Minister of the Interior and Administration of 27 April 2010 amending the regulation on the list of products used to ensure public safety or to protect health, life and property, and on the rules for issuing approvals for the use of such products. 

5) Regulation of the Minister of the Interior and Administration of 7 June 2010 on the fire protection of buildings, other structures and land. 

6) PN-EN 1838:2013-111: Specifies requirements for emergency lighting and standby lighting systems installed in buildings or premises. 

7) PN-EN 50172:20051: Contains provisions on the lighting of escape routes and safety signs, as well as the minimum requirements and parameters for this type of lighting depending on the size, type and purpose of the building. 

8) PN-EN 60598-2-22:2004/AC2: Sets out requirements for luminaires for emergency lighting. 

It is also worth quoting directly § 181 of the Regulation of the Minister of Infrastructure of 12 April 2002 on the technical conditions that buildings and their location should meet (Dz.U.2022.1225, consolidated text): “A building in which a loss of voltage in the electricity supply network may endanger the life or health of people, pose a serious threat to the environment, or cause significant material losses, must be supplied from at least two independent, automatically switching electricity sources and be equipped with automatically switching emergency lighting (standby or escape lighting).”

Where must escape lighting be used? 

By law, escape lighting must be used: 
– In rooms: 

  • auditoriums of cinemas, theatres and philharmonic halls, and other performance venues, 
  • lecture halls, conference rooms, entertainment venues and sports halls designed for more than 200 people, 
  • museum exhibition rooms, 
  • with an area of more than 1000 m2 in garages lit solely by artificial light. 

– On escape routes: 

  • from the rooms listed in the point above, 
  • lit solely by artificial light, 
  • in hospitals and other buildings intended primarily for the stay of people  
  • with limited mobility, 
  • in high-rise and tall public-use and collective-residence buildings. 

– In temporary buildings, if they are intended for performances or other gatherings of people. 

How often should illuminance of emergency and escape lighting be measured? 

Under § 3(1) and (2) of the Fire Protection Regulation (r.o.p.), fire-fighting equipment, which may include emergency lighting and escape lighting, must be installed in a facility in accordance with a design agreed by a fire protection expert, and a condition for approving it for use is that tests and examinations appropriate to the given equipment are carried out, confirming that it works correctly. Fire-fighting equipment must undergo technical inspections and maintenance in accordance with the rules and in the manner specified in the Polish Standards for fire-fighting equipment, in the technical and operating documentation, and in the operating instructions prepared by the manufacturers. 

Technical inspections and maintenance of fire-fighting equipment, which may include emergency lighting and escape lighting, must be carried out at intervals set by the manufacturer, but at least once a year. 

How should inspections be carried out? 

a) Where an automatic test device is used, the information should be recorded monthly. 
 
b) For all other systems, tests, together with a record of their results, should be carried out as follows: 
 
Daily test – the indicators showing that the central power supply is functioning correctly should be checked visually. The purpose of the visual inspection of the indicators is to establish that the system is ready for operation and whether the system requires a test. 

Monthly test– switch each luminaire and each internally illuminated exit sign with battery power into emergency mode by simulating a failure of the primary supply, for long enough to make sure that every lamp is lit. During this period, check all luminaires and signs to make sure that they are present, clean and working correctly. 

Annual test – each luminaire and internally illuminated sign should be tested for its minimum duration of operation; for the full rated duration, however, follow the manufacturer’s information. Restore the power supply to the normal lighting and check each indicator lamp or device to make sure that it shows that the primary supply has been restored. It is recommended to check that the charging circuit is working correctly; 

Source: Standard PN-EN 50172:2005P Emergency escape lighting systems. 

Are there any new technologies in escape lighting? 

Yes, a look at the market turns up offerings such as:  

1) LED lighting: Modern escape lighting systems increasingly use LED technology. LED lighting is energy-efficient, long-lasting and offers high light intensity, which is crucial for effective escape lighting. 

2) Lighting monitoring systems: Companies such as TM Technologie have developed innovative monitoring systems for emergency and escape lighting, such as the DATA-S system. These systems allow remote monitoring and control of escape lighting, which makes it easier to maintain and manage them. 

Summary

Escape lighting is an essential element of safety in every building. It plays a key role in ensuring people’s safety during evacuation in emergencies such as fire, earthquake or power failure. It is a system designed specifically to provide adequate lighting so that a quick and safe evacuation from the building is possible in the event of danger. One of the key aspects of escape lighting is its reliability. For this reason, these systems are often connected to emergency power supply systems so that they work even if the main power source is lost. Regular testing, maintenance and upkeep of escape lighting are crucial to ensuring its effectiveness in crisis situations. 